Mitsubishi inverter overload fault judgment method
Published:2023-02-02 14:41:50
1. Check whether the three-phase power of the motor is balanced
(1) If the three-phase voltage of the motor is not balanced, the three-phase voltage of the output end of the Mitsubishi inverter should be checked again.
(2) If the three-phase voltage of the Mitsubishi frequency converter is also unbalanced, the problem is in the Mitsubishi frequency converter. The inverter module and its driving part should be checked.
(3) If the voltage at the output end of the Mitsubishi frequency converter is balanced, the problem lies in the line between the Mitsubishi frequency converter and the motor. It should be checked whether all the screws at the terminal have been tightened.
(4) If there are touchers or other electrical appliances between the frequency converter and the motor, it is also necessary to check whether the terminals of the relevant electrical appliances have been tightened, and whether the touch condition of the contacts is outstanding.
(5) if the three-phase voltage of the motor is balanced, the working frequency of tripping should be understood;
(6) If the working frequency is low and there is no vector control (or no vector control in the frequency converter), the U/F ratio is mainly decreased;
(7) If the load can still be driven after falling, it means that the preset U/F ratio is too high, and the peak value of the excitation current is too large. The current can be reduced by decreasing the ratio of U/F;
(8) If the load is not moving after falling, the capacity of the frequency converter should be considered to increase;
If the cause is not found through the above view, it should be checked whether it is a mistake.
The way to judge is to measure the output current of Mitsubishi frequency converter with ammeter under light load or no load, and compare it with the running current value displayed on the display screen. If the current reading displayed on the display screen is much larger than the actual measured current, it indicates that the error of the current measurement part inside Mitsubishi frequency converter is large, and the "overload" trip may be wrong action.
2. Check whether the motor is overheating
(1) If the temperature of the motor is not high, the first thing to check is whether the electronic thermal maintenance function of the frequency converter is preset reasonably.
(2) If there is margin for Mitsubishi frequency converter, the preset value should be relaxed;
(3) If the allowable current of Mitsubishi frequency converter has no margin and can not be relaxed, and the overload is normal overload according to the field process requirements, it indicates that the choice of Mitsubishi frequency converter is not appropriate. The capacity of Mitsubishi frequency converter should be increased and a larger Mitsubishi frequency converter should be replaced.

-
202301-12Delta UPS uninterruptible power supply basic conditions
1. Visually inspect the UPS and battery (or other energy storage) equipment for obstructions and properly cool the surrounding area.2. Ensure that there is no abnormal operation or warning on the UPS ···
-
202308-18Siemens SINAMICS G120 modular inverter advantages
1. Modular design creates a high degree of flexibility to adapt to future requirements for drive solutionsThe control unit can be replaced with power (hot swap)Use plug terminalsThe procedure for repl···
-
202302-13Mitsubishi PLC communication detection steps
When you are ready to communicate through the AJ71QE71, perform the ping procedure in MS-DOS mode before starting the communication with Mitsubishi PLC's GPPW to see if the connection is correct. ···
-
202304-14Delta inverter to reduce the failure rate method
Daily check Item 1 of Delta Frequency converter problem repair:Check whether the sound of the motor is abnormal during operation, including whether the motor is vibrating during operation.Daily view o···
-
202301-09Schneider frame circuit breaker MT circuit breaker failed to close the switch problem
Schneider structural circuit breaker has not stored energy (check the power supply of the energy storage motor, if normal check whether it can be manually stored energy)MX shunt coil live (disconnect ···

+86 18621383628
+86 13811814778
Building 26, Liyuan Community, Chaoyang District, Beijing, China