After the frequency converter is used for more than half a year, if the equipment is to be run again, the chance of damage may be greatly increased because of the placing environment, the service life of the frequency converter, the load rate and other factors. The fault usually presents the following problems:
1. After the equipment is energized, the inverter explodes and the front circuit breaker jumps.
2. After startup, there is no display on the panel of frequency converter
3. The frequency converter operates normally after startup, but fails after operation
4. The frequency converter operates normally after startup, but it presents a blast machine after operation
Why does the above phenomenon of frequency converter failure occur?
1. Improper placing environment of frequency converter will lead to the above problems.
2. Frequency converter is composed of rectifier module, IGBT and electrolytic capacitor and other primary components. If the electrolytic capacitor is not energized for a long time, the electrolyte in the electrolytic capacitor will dry up, so that the capacity will decrease and the leakage will increase. In this way, when the converter is powered, the operation of the switching power supply will be abnormal or damaged. In serious cases, it will lead to the damage of the electrolytic capacitor of the main circuit, resulting in the blasting of the converter.
Why are some frequency converters still able to be used normally after being placed for a period of time?
1. Frequency converter storage environment is perfect
2. The frequency converter does not work in overheat or overload condition for a long time
3. The service life of frequency converter is short
4, the capacitor characteristics of the frequency converter is better than **
How to guard against frequency converter power-on failure?
1, Frequency converter is not used for a long time, should be sealed in a dust-proof and moisture-proof environment, storage temperature is -25c-65c.
2. It is safer and more useful to use special equipment to charge the inverter regularly (every 3 months) and check the input and output ports. The 220 volt voltage is supplied to the 380 volt converter (110 volts is supplied to the 220 volt converter), and the voltage slowly rises from 0 volts to 220 volts. The duration is determined by the power of the converter. Then, supply 380 volts (220 volts) to the converter and look at the input voltage. Only an imbalance of +/-3% is allowed.
-
202302-27
Delta servo motor how to choose?
In the selection of Delta servo motor, in principle should be based on the load conditions to choose. There are two kinds of loads on the motor shaft, namely damping torque and inertia load. The two l···
-
202212-29
Delta frequency converter maintenance steps
First, the repair of frequency converter must first check whether the sound in the operation of the motor is abnormal, including whether it is sensational in the operation of the motor.Two, check whet···
-
202302-17
959698 reasons for failure of Siemens 3RW44 soft starter
3RW44 Soft starter 95,96,98 is a comprehensive fault, what causes it to operate?95,96,98 reasons for failure of Siemens 3RW44 soft starter95,96,98 is the normally open normally closed integrated fault···
-
202212-29
Fault and maintenance method of MCGS touch screen
1. The fault of touch deviationIf the finger touches the position and the mouse arrow does not coincide. After installing the driver, you should not touch the center of the bull 's-eye vertically ···
-
202301-31
Delta overload trip fault solution
1. The main cause of VFD overload(1) Mechanical overload. The main characteristic of overload is the motor heating, which can be found by reading the running current on the display screen.(2) The unba···