Published:2023-05-05 11:07:30
After the frequency converter is used for more than half a year, if the equipment is to be run again, the chance of damage may be greatly increased because of the placing environment, the service life of the frequency converter, the load rate and other factors. The fault usually presents the following problems:
1. After the equipment is energized, the inverter explodes and the front circuit breaker jumps.
2. After startup, there is no display on the panel of frequency converter
3. The frequency converter operates normally after startup, but fails after operation
4. The frequency converter operates normally after startup, but it presents a blast machine after operation
Why does the above phenomenon of frequency converter failure occur?
1. Improper placing environment of frequency converter will lead to the above problems.
2. Frequency converter is composed of rectifier module, IGBT and electrolytic capacitor and other primary components. If the electrolytic capacitor is not energized for a long time, the electrolyte in the electrolytic capacitor will dry up, so that the capacity will decrease and the leakage will increase. In this way, when the converter is powered, the operation of the switching power supply will be abnormal or damaged. In serious cases, it will lead to the damage of the electrolytic capacitor of the main circuit, resulting in the blasting of the converter.
Why are some frequency converters still able to be used normally after being placed for a period of time?
1. Frequency converter storage environment is perfect
2. The frequency converter does not work in overheat or overload condition for a long time
3. The service life of frequency converter is short
4, the capacitor characteristics of the frequency converter is better than **
How to guard against frequency converter power-on failure?
1, Frequency converter is not used for a long time, should be sealed in a dust-proof and moisture-proof environment, storage temperature is -25c-65c.
2. It is safer and more useful to use special equipment to charge the inverter regularly (every 3 months) and check the input and output ports. The 220 volt voltage is supplied to the 380 volt converter (110 volts is supplied to the 220 volt converter), and the voltage slowly rises from 0 volts to 220 volts. The duration is determined by the power of the converter. Then, supply 380 volts (220 volts) to the converter and look at the input voltage. Only an imbalance of +/-3% is allowed.
-
202306-01
The main function and composition of the configuration software of MCGS Tong - state embedded edition are introduced
The main function of MCGS embedded configuration software1. Simple and flexible visual operation interface: all Chinese and visual development interface is adopted, which meets the usage habits and re···
-
202212-29
This section describes how to set a gateway for Advantech switch eki-2528
step 1: Configure a VLAN. You are advised to allocate a dedicated VLAN, for example, VLAN 1000, for the management IP address of the switch on the network.Configuration command: vlan 1000step 2: Set a···
-
202212-30
ABB breaker failure and treatment
Judgment and handling of "reject" failureThe occurrence of "rejection" situation, basically in the closing operation and reclosing process. This kind of failure is very harmful. Fo···
-
202301-28
Siemens SINAMICS GM150 Deep Maintenance
On-site maintenanceCheck and clean pre-charge loop, rectifier unit, diode characteristics, inverter unit, GSV, AVT.Rectifier module diagnostic test, and high voltage switchgear interface function test···
-
202302-07
WEINVIEW TK6070ih touch screen into the system setting what are the methods?
1. Generally, there is a small black arrow button in the lower right corner of the touch screen. After clicking and entering the correct password, you can enter the system Settings. However, during co···