After the frequency converter is used for more than half a year, if the equipment is to be run again, the chance of damage may be greatly increased because of the placing environment, the service life of the frequency converter, the load rate and other factors. The fault usually presents the following problems:
1. After the equipment is energized, the inverter explodes and the front circuit breaker jumps.
2. After startup, there is no display on the panel of frequency converter
3. The frequency converter operates normally after startup, but fails after operation
4. The frequency converter operates normally after startup, but it presents a blast machine after operation
Why does the above phenomenon of frequency converter failure occur?
1. Improper placing environment of frequency converter will lead to the above problems.
2. Frequency converter is composed of rectifier module, IGBT and electrolytic capacitor and other primary components. If the electrolytic capacitor is not energized for a long time, the electrolyte in the electrolytic capacitor will dry up, so that the capacity will decrease and the leakage will increase. In this way, when the converter is powered, the operation of the switching power supply will be abnormal or damaged. In serious cases, it will lead to the damage of the electrolytic capacitor of the main circuit, resulting in the blasting of the converter.
Why are some frequency converters still able to be used normally after being placed for a period of time?
1. Frequency converter storage environment is perfect
2. The frequency converter does not work in overheat or overload condition for a long time
3. The service life of frequency converter is short
4, the capacitor characteristics of the frequency converter is better than **
How to guard against frequency converter power-on failure?
1, Frequency converter is not used for a long time, should be sealed in a dust-proof and moisture-proof environment, storage temperature is -25c-65c.
2. It is safer and more useful to use special equipment to charge the inverter regularly (every 3 months) and check the input and output ports. The 220 volt voltage is supplied to the 380 volt converter (110 volts is supplied to the 220 volt converter), and the voltage slowly rises from 0 volts to 220 volts. The duration is determined by the power of the converter. Then, supply 380 volts (220 volts) to the converter and look at the input voltage. Only an imbalance of +/-3% is allowed.

-
202302-23Schneider inverter commissioning procedure
1. Type recognition: Whether the type of frequency converter is common with the type of frequency converter purchased.2. Transportation admission: After opening the package, check whether the frequenc···
-
202301-31Influence of Delta impulse current on frequency converter
In the process of maintenance of frequency converter, it is found that due to the back electromotive force in the stator winding, the electromotive force in the motor under the condition of synchronou···
-
202302-09How to maintain MCGS touch screen
1. Wipe the phone screen with a dry cloth before opening it every day.2. Drinks or drops falling on the screen will cause the software to stop the reaction. This is because water droplets and fingers ···
-
202309-14Yaskawa servo drive debugging method steps
1. Basic wiringThe main power input is 220V, which is connected from L1 and L3 (the actual use should refer to the operation manual); Control power input r, t can also be directly connected - 220V; Mo···
-
202301-16TPC1561HI MCGS on-state touch screen operation panel common faults
TPC1561HI MCGS touch screen operation panel common faults(1) Black screen, flower screen and white screen(2) LCD screen aging, low high pressure, lamp aging(3) The LCD screen has no display, and the b···

+86 13811814778
+86 13811814778
Building 26, Liyuan Community, Chaoyang District, Beijing, China