Conductive liquid level detection in industrial processes often faces severe electrochemical corrosion and scale accumulation caused by traditional direct current excitation on probe electrodes. Furthermore, long-distance signal transmission is highly vulnerable to ground loops and electromagnetic interference, leading to false triggering in pump control loops. To address these operational challenges, the NPGLK-C333D conductive level isolator delivers a robust engineering solution by supplying an alternating detection voltage to prevent electrode polarization while converting contact signals into reliable relay outputs.

Industrial applications such as wastewater treatment basins, chemical acid-base storage tanks, and boiler feed water systems demand precise liquid level regulation to prevent dry running or tank overflow. The device utilizes an alternating current detection principle to sense minute changes in current when conductive media contacts the electrode probes. Operating on a wide power supply range of 18 ~ 60 V DC with a low power consumption of ≤ 1.2 W, the unit ensures high operational stability. It features complete three-port galvanic isolation between the input, output, and power supply circuits, with a dielectric strength of ≥ 1500 V AC and an insulation resistance of ≥ 100 MΩ, effectively eliminating ground loop disturbances and ensuring electromagnetic compatibility according to IEC 61326-3-1 standards.
Technical Specifications
Power Supply: 18 ~ 60 V DC
Input Signal: Electrode switch
Output Signal: Relay contact
Permissible Load: 250 V AC / 2 A or 30 V DC / 2 A
Switching Characteristics: High/low level switching via DIP switch S1; position a closes output relay with steady yellow LED; position b opens output relay with off yellow LED
Switching Life: > 100,000 operations
Switching Frequency: < 10 Hz
Working Power Consumption: ≤ 1.2 W
Electromagnetic Compatibility: IEC 61326-3-1
Dielectric Strength: ≥ 1500 V AC @ Input/Output/Power circuits
Insulation Resistance: ≥ 100 MΩ @ Input/Output/Power circuits
Operating Temperature: -40 ℃ ~ +70 ℃
Storage Temperature: -40 ℃ ~ +80 ℃
Connection Method: Screw terminal connection
Dimensions: 17.8 mm width x 110 mm height x 117 mm depth
Mounting Type: DIN 35 mm rail mounting
Product Certifications: CE, FCC
AC Excitation Principle and Core Specifications
The primary technical advantage of this conductive level isolator lies in its AC excitation mechanism. By supplying an alternating voltage to the sensor electrodes, the device prevents the continuous ionic migration that causes rapid metal electrode oxidation and insulating scale buildup in DC-based systems. When the conductive fluid reaches the probe, the resulting alternating current variation is isolated and converted into a standard switching action. The integrated output relay handles loads up to 250 V AC at 2 A or 30 V DC at 2 A, making it fully capable of directly driving external contactors, solenoid valves, or controller digital inputs without intermediate interposing relays.
DIP Switch Configuration and Fault Diagnostics
Field configuration is streamlined through accessible front-panel DIP switches that allow engineers to tailor the operational logic to specific application requirements. Setting switch S1 to side a ensures that when the target liquid level reaches the upper or lower limit, the output relay energizes and the yellow indicator illuminates continuously. Conversely, setting S1 to side b reverses this action. Additionally, the second output channel can be independently configured either as a secondary relay contact or as a dedicated fault signal output. Combined with built-in input open-circuit fault detection, the module immediately identifies probe disconnection or wiring failures to enhance system safety.
Practical Selection and Installation Advice
When deploying this electrode switch module in industrial control cabinets, engineers must verify the conductivity threshold of the target liquid and ensure proper probe positioning for upper, lower, or dual-limit control schemes. The compact housing measures only 17.8 mm in width, enabling high-density side-by-side mounting on standard DIN 35 mm rails to save valuable cabinet space. Secure screw terminals ensure reliable electrical connections under continuous mechanical vibration. For comprehensive project planning, Beijing Zhongping Technology provides expert technical guidance and readily available local inventory to support seamless system integration and timely replacement.
Reliability and Environmental Durability
Designed for harsh industrial environments, the module operates reliably across a wide ambient temperature range from -40 ℃ to +70 ℃ and can withstand storage temperatures down to -80 ℃. The rigorous three-way galvanic isolation protects internal electronic components from high-voltage transients and industrial noise surges. Compliance with CE and FCC certifications guarantees adherence to international safety and emission standards. Furthermore, the mechanical relay output is rated for more than 100,000 switching cycles, ensuring long-term operational durability and minimizing maintenance overhead in continuous process control applications.
Selection Guidance and Alternative Options
Selecting the correct signal conditioner requires evaluating the power supply architecture, load current requirements, and control logic configuration. While the standard C-series covers most conductive liquid monitoring needs, industrial facilities requiring alternative voltage ratings or multi-channel configurations can explore matching options within the broader product portfolio. Beijing Zhongping Technology offers professional cross-reference selection assistance and comprehensive local stock support to match specific plant automation requirements efficiently.
Frequently Asked Questions (FAQ)
1. What is the current local stock status and typical delivery lead time for this isolator model?
Beijing Zhongping Technology maintains robust regional inventory of this unit to ensure same-day dispatch and minimize operational downtime for urgent plant replacements.
2. What warranty coverage and RMA support are provided upon purchase?
All units are backed by a comprehensive 12-month warranty, supported by rigorous pre-shipment testing and streamlined local return merchandise authorization services through Beijing Zhongping Technology.
3. What is the allowable operating voltage range for the power supply input?
The device operates on a flexible DC voltage range from 18 V DC to 60 V DC.
4. How does the AC excitation prevent probe degradation?
Applying an alternating voltage instead of direct current prevents continuous one-way ionic flow, thereby eliminating severe electrochemical corrosion and scale deposition on metal sensor probes.
5. What are the electrical ratings for the relay output contacts?
The output relay supports maximum load ratings of 250 V AC at 2 A or 30 V DC at 2 A.
6. What physical dimensions and mounting methods are specified for cabinet installation?
The unit features a slim housing width of 17.8 mm, a height of 110 mm, and a depth of 117 mm, designed for standard DIN 35 mm rail mounting.
7. How is open-circuit fault detection handled by the module?
The internal diagnostic circuitry continuously monitors the input loop and triggers fault indication if probe wiring becomes open or disconnected.
8. What electromagnetic compatibility standards does this isolator satisfy?
The device complies with IEC 61326-3-1 standards for electromagnetic compatibility in industrial environments.
FAQ
1.Who are We?
Beijing Zhongping Technology Co., LTD., is a global industrial electrical automation service provider, is a scientific research, design, marketing, technical services, industrial Internet, international import and export services as one of the science and technology companies.
2.What can you buy from us?
PLC, inverter, human-machine interface, hydraulic products, low-voltage power distribution, industrial robots and core components
3.Is the item in stock or need to be purchased from another supplier?
We have a large inventory of goods and have our own warehouse.
4.What advantages do we have over other suppliers?
Our company has a large amount of inventory and a number of warehouses, but also in the country's important industrial provinces and cities with offices and a number of overseas service points. To provide you with intelligent manufacturing one-stop comprehensive services, save efforts, labor and cost.
5.Can you provide 100% new original authentic products?
We only sell new original genuine, no renovation, no fake, only for the original factory original!
6.How long is the delivery time?
If there is a stock, it will take 2-3 working days to ship, if the quantity is large, it will take 5-7 working days after receiving the payment, if it is not a conventional model, it will take some time, we will inform you of the specific delivery time.
7.Is there technical support available?
Of course, we have a professional technical team that can help you solve technical problems.
8.How do we guarantee quality?
We have three processes to control the quality of goods.
1) Our engineers will inspect the production and quality control in the factory regularly.
2) Incoming materials shall be inspected by experienced purchasing engineers before they can be stored.
3) At least 2 people in the logistics department cross-check the goods to be sent before delivery.
9.Can you guarantee the safe and reliable delivery of your products?
Yes, we strictly adopt the international standard packing. We also use special packaging for dangerous goods, and refrigerated shipping for items with temperature requirements. Special item packaging and general cargo standard packaging requirements may incur additional costs.
10.How about the freight?
The cost depends on how you choose to get the goods. Express is usually the fastest but also the most expensive way. Sea freight is the best solution for large quantities of goods. The exact shipping cost depends on the purchase amount、quantity and weight of your order. Please feel free to contact us for more information.